PhotonIcs and Electromagnetics Research Symposium,
also known as Progress In Electromagnetics Research Symposium
PIERS Proceedings
Published: 2015-07-09
Examples of Variation in Measured ELF Electric Fields under 400 kV Power Lines
By
Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)1104-1106
Abstract
The paper presents how the measured extremely low frequency (ELF) electric fields (EFs) fluctuate in the same measurement place when the humidity varies. EF measurements were performed at three places near 400 kV power lines. In Place A (nine measurements), the EFs varied from 6.8 to 12.5 kV/m when relative humidity was from 70.5% to 86%. In Place B (five measurements), the EFs were 5.1–8.2 kV/m when relative humidity ranged from 67% to 76%, and in Place C (two measurements), the EFs were 0.90–0.92 kV/m when humidity was 68–76%. The measured EFs varied significantly.
Citation
Lauri Sydänheimo, Leena Korpinen, Hiroo Tarao, Oleksandr Okun, and Rauno Paakkonen, "Examples of Variation in Measured ELF Electric Fields under 400 kV Power Lines," Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)1104-1106
References

1. CIGRE (International Council on Large Electric Systems), "Technical guide for measurement of low frequency electric and magnetic fields near overhead power lines," Working Group C4.203, CIGRE, Paris, France, 2009.        Google Scholar

2. European Parliament and Council of the European Union, "Directive 2013/35/EU of the Eurothe exposure of workers to the risks arising from physical agents (electromagnetic fields)," Official Journal of the European Union, 21, 20th Individual Directive within the Meaning of Article 16(1) of Directive 89/391/EEC and Repealing Directive 2004/40/EC, 2013.        Google Scholar

3. ICNIRP, "Guidelines for limiting exposure to time varying electric and magnetic fields (1 Hz-100 kHz)," Health Phys., Vol. 99, 818-836, 2010.        Google Scholar

4. Korpinen, L., H. Kuisti, J. Elovaara, and V. Virtanen, "Cardiac pacemakers in electric and magnetic fields of 400-kV power lines," Pacing Clin. Electrophysiol., Vol. 135, 422-430, 2012.
doi:10.1111/j.1540-8159.2011.03327.x        Google Scholar

5. Korpinen, L., H. Kuisti, J. Elovaara, and V. Virtanen, "Implantable cardioverter defibrillatorsin electric and magnetic fields of 400 kV power lines," Pacing Clin. Electrophysiol., Vol. 37, 297-303, 2014.        Google Scholar