Advanced Methods of UHF EM Diagnostic of Discharge Activity in High Voltage Transformers Dielectric
By
Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)2445-2449
Abstract
One of the crucial aspects of high voltage power transformer is the quality of its dielectric oil filling. Partial discharges represents significant problem which can lead to serious transformer failure and accident. Variety of methods for early detection of partial discharge has been developed over time. The most progressive is the UHF method. The article reports on the results obtained by the application of new Discrimination of Disturbed Acquisition detec- tion approach within the UHF method. Further, proposal of novel modification of sensors are described. The approach consists in the adjustable signal filtration before processing, which can significantly improve the reliability of partial discharge signal identification.
Citation
Martin Čáp, Petr Drexler, Pavel Fiala, Milos Kaska, Lubomir Kocis, and Miloslav Steinbauer, "Advanced Methods of UHF EM Diagnostic of Discharge Activity in High Voltage Transformers Dielectric," Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)2445-2449
References

1. Dalarsson, M., A. Motevasselian, and M. Norgren, "Using multiple modes to reconstruct conductor locations in a cylindrical model of a power transformer winding," International Journal of Applied Electromagnetics and Mechanics, Vol. 41, No. 3, 279-291, 2013.
doi:10.3233/jae-121612        Google Scholar

2. Sarkar, B., D. K. Mishra, C. Koley, and N. K. Roy, "Microstrip patch antenna based UHF sensor for detection of partial discharge in high voltage electrical equipments," 11th IEEE India Conference: Emerging Trends and Innovation in Technology, INDICON, 2015.
doi:10.1109/indicon.2014.7030463        Google Scholar

3. Lopez-Roldan, J., T. Tang, and M. Gaskin, "Optimisation of a sensor for onsite detection of partial discharges in power transformers by the UHF method," IEEE Transaction on Dielectrics and Electrical Inculation, Vol. 15, No. 6, 1634-1639, 2008.
doi:10.1109/tdei.2008.4712667        Google Scholar

4. Myška, R. and P. Drexler, "Simulation and verification of methods for partial discharge source localization," PIERS Proceedings, 704-708, Kuala Lumpur, Malaysia, March 2012.        Google Scholar

5. Fiala, P., T. Jirku, P. Drexler, and P. Dohnal, "Detection of partial discharge inside of HV transformer, modeling, sensors and measurement," PIERS Proceedings, 1013-1016, Cambridge, USA, July 2010.        Google Scholar

6. Drexler, P., M. Čáp, P. Fiala, M. Steinbauer, M. Kaška, and L. Kočiš, "Detection of low-level electromagnetic signal of partial discharge by means of disturbed acquisition discrimination," PIERS Proceedings, 213-216, Guangzhou, August 2014.        Google Scholar